Ventilation Performance Under Passive Occupancy Conditions: Impacts on IAQ and Cognitive Function in Lecture Halls

Vladanka Presburger Ulniković (Univerzitet Union Nikola Tesla), Aleksandra Milošević-Pantović (Union University, Univerzitet Union Nikola Tesla)
Original paper Published on 01 Jan. 2026 Indoor Air License: CC BY

How to read this summary? Illustrated guide

The essentials

In two sealed-window lecture sessions, indoor pollutants accumulated and poorer air quality covaried with lower working-memory scores and greater reported fatigue.

Question

How does passive occupancy with windows closed affect indoor air quality and cognitive performance in university lecture halls? The study also examines whether the halls’ window configurations could meet the adopted ventilation requirement under different opening conditions.

Method

Researchers monitored two sessions at one Belgrade university: 68 students in a May 2025 midterm session and 42 in a November 2025 lecture, with windows and doors closed and mechanical ventilation off. Indoor pollutants and environmental conditions were measured about every 15 minutes; students completed digit-span tests and symptom questionnaires. The authors also estimated ventilation capacity against an adopted rate of 8 L/s per person and calculated an exploratory total excess load index.

Findings

  • Result CO2 rose to 2231 ppm in the May session and reached 3136 ppm in November, both above the cited 1000 ppm guideline.
    See the passage in the paper
    In Hall 9 (May, sealed windows), CO 2 rose from 1253 ppm to 2231 ppm within 36 min.In Hall 4 (November), CO 2 reached 3136 ppm after 101 min.
  • Result The study reported a strong inverse association between CO2 and backward digit-span performance, although the observational design does not establish causation.
    See the passage in the paper
    Correlation analysis showed r = -0.75(p < 0.01 ) between CO 2 and backward digit span (session-level aggregates).
  • Result Moderate postsession fatigue was reported by 79% of participants in November and 62% in May.
    See the passage in the paper
    Postsession moderate fatigue reached 79% in November versus 62% in May.
  • Result The ventilation calculations indicated that meeting the adopted airflow requirement with tilt-open windows would require several windows to remain continuously open.
    See the passage in the paper
    To meet the ASHRAE 62.1 required rate, at least 5 of the 30 tilt windows in Hall 9 would need to be continuously open throughout the lecture (equivalent to 293 window-minutes per hour).In Hall 4, 2 of the 7 windows would need to be continuously open in the tilt position.
  • Authors’ interpretation The authors argue that reliable ventilation improvements should rely on technical controls rather than occupant behavior alone.
    See the passage in the paper
    The robust solution is not to change occupant behavior (which is inconsistent [73]) but to eliminate occupant-driven ventilation failure.

Limitations

  • The two campaigns differed in hall, season, and academic context, so seasonal effects could not be isolated.
    See the passage in the paper
    Measurements were conducted in only two lecture halls within a single university, each during one campaign with different academic contexts (midterm exams vs. regular lectures).Pure seasonal effects therefore cannot be isolated [68].
  • The observational design, practice effects, and unmeasured confounders limit causal interpretation of the cognitive results.
    See the passage in the paper
    Practice effects [49][50][51] and unmeasured confounders (sleep, caffeine, SES, and baseline stress [58]) constrain causal inference.
  • The total excess load index is exploratory and has not been validated to represent physiological impact.
    See the passage in the paper
    The TEL index is exploratory (equal weighting, unvalidated), and should be interpreted as a comparative descriptive indicator, since equal weighting of pollutants does not necessarily reflect their relative physiological impacts.

Why it matters

The authors present passive occupancy and inconsistent window operation as a practical source of ventilation failure in naturally ventilated lecture halls, even where window area may appear adequate. They argue for evaluating automated window actuators or demand-controlled mechanical ventilation with heat recovery, rather than depending on occupants to manage ventilation reliably.

Written by AI from the paper. Passages are checked word for word against the text we analysed; the rest may contain errors.

AI-generated keywords: lecture hall ventilation indoor air quality carbon dioxide cognitive performance window operation

Read further

  • Comprehensive Summary
  • Layman's Summary
  • Blog article
  • Original abstract
The paper investigates whether students remaining in lecture halls with windows closed can lead to inadequate ventilation, poorer indoor air quality (IAQ), and reduced cognitive performance. It also assesses whether the halls’ windows could provide the airflow recommended by ASHRAE 62.1 when fully open or tilt-open. The authors describe sessions with windows sealed as a realistic worst-case operating condition, while emphasizing that the observational study was not a controlled test of ventilation effects. Measurements were conducted at one university in Belgrade during two campaigns: a May 2025 midterm session in Lecture Hall 9, attended by 68 students, and a November 2025 regular lecture in Hall 4, attended by 42. During both sessions, the windows and doors remained closed, and mechanical ventilation was off. Indoor carbon dioxide (CO₂), particulate matter, temperature, humidity, formaldehyde, and total volatile organic compounds (TVOC) were monitored alongside outdoor conditions, with readings taken approximately every 15 minutes. Students completed digit-span tests, including backward span as a measure of working memory, and questionnaires about symptoms and perceptions before and after each session. The authors also calculated an exploratory total excess load (TEL) index to describe how far multiple pollutants exceeded reference values. Air quality deteriorated in both halls. In Hall 9, CO₂ rose from 1,253 ppm to 2,231 ppm in 36 minutes. In Hall 4, it reached 3,136 ppm after 101 minutes, exceeding the paper’s reference level of 1,000 ppm. TVOC exceeded 1.0 mg/m³ in both campaigns. In May, the temperature reached 28.7°C, above the cited comfort threshold of 25°C, and PM₂.₅ peaked at 33 µg/m³, above the cited guideline of 15 µg/m³. Indoor PM₂.₅ was reported to be 733% higher than outdoors that month, suggesting that indoor sources may have contributed. In November, indoor PM₂.₅ was 70% lower than outdoors, even as CO₂ accumulated in the closed hall. Humidity reached 63.5%, above the cited upper limit of 60%. The TEL index was 361% for May and 335% for November. However, the authors stress that this index is descriptive and has not been physiologically validated. Average backward digit-span scores were lower in November than in May (4.32 versus 6.55). The authors also report a strong inverse association between CO₂ and backward-span performance (r = −0.75). Their regression model identified CO₂ and occupancy as significant predictors, with an adjusted R² of 0.59. These associations do not establish that CO₂ caused the differences in cognitive performance. Moderate postsession fatigue was reported by 79% of students in November and 62% in May. In November, reported concentration difficulties increased from 31% before the session to 57% afterward. Students commonly reported stuffy air in both campaigns. Ventilation calculations suggested that fully opened windows could theoretically meet the adopted airflow requirement. In tilt-open mode, at least five of Hall 9’s 30 windows, or two of Hall 4’s seven windows, would need to remain continuously open. The authors argue that relying on occupants to maintain this configuration is unreliable. They recommend monitoring and scheduled ventilation as immediate measures, and suggest evaluating automated window controls or demand-controlled mechanical ventilation with heat recovery where appropriate. The findings are limited by the small sample of two halls at a single university and by differences in season, hall, occupancy, and academic context between the campaigns. The modest and unbalanced samples, consumer-grade sensors, possible digit-span practice effects, and unmeasured factors such as sleep and stress also constrain interpretation.

Was this synthesis useful?

Score: 0

Why do we need votes?

Votes are used to determine whether we need to re-run our summarizing tools. If the count reaches -10, our tools can be restarted.

Ask questions about this paper to our AI assistant

How to chat with this paper? Illustrated guide

You can also chat with multiple papers at once here.

Figures and plots

Ask about a figure by number or use its question button to request visual analysis. Up to two figures and four image panels per question. Values read from plots are approximate; check the original data.

AI assistant instructions?

Tools for this paper

Explain it differently 1 free rewrite left today
Save to a collection Group papers in collections to compare them, chat with them and export them. Continue with Google Create a free account Log in

Advanced tools Premium

For researchers who follow a field closely: citation alerts, journal-club slides, version comparison and Zotero export. Discover Premium

Zotero Zotero guide
Citation alerts Citation alerts guide
Who works on it?

Among the 15 papers around this one, the name that comes back most: Fatemeh Shahsavari (2 papers)

Continue with Google Create a free account: your first map is free

Papers around this one

See them on a map

Ranked by how close their title and abstract are to this paper’s. Select some to read them together.

Closest papers

  1. Close Broader context
    Assessment of Pollutant Spread from a Building Basement with three Ventilation Systems
    Juslin Koffi · 2010 · EuroAcademy on Ventilation and Indoor Climate - CLIMACADEMY Course 7: Experimental Assessment of Indoor Environment Para · AI summary available

    Assessment of Pollutant Spread measures how ventilation systems affect contaminant movement from a basement, while this study examines sealed lecture halls and occupant air quality.

    Abstract

    Ventilation aims at providing a sufficient air renewal for ensuring a good indoor air quality (IAQ), yet building energy policies are leading to adapting various ventilation strategies minimising energy losses through air renewal. A recent IAQ evaluation campaign in French dwellings shows important pollution of living spaces by VOCs such as formaldehyde, acetaldehyde or hexanal, particularly in buildings equipped with a garage. Besides, radon emission from soil is a subject of concern in many countries. Several studies are done to understand its release mode and deal with the spread of this carcinogen gas. This paper aims to experimentally assess a contaminant spread from a house basement us…

  2. Related Broader context
    A Multi-model and Multi-scenario Assessment of the Impact of Climate Change on the Heating and Cooling Load Components of an Archetypical Residential Room in Major Indian Cities
    Raj S. Srivastava, A. Aravinda De Chinnu, Aakash C. Rai · 2023 · Systems and Control · preprint, not peer reviewed · cited 1 time · AI summary available

    A Multi-model and Multi-scenario Assessment projects climate-change effects on residential heating and cooling loads, rather than lecture-hall air quality or cognition.

    Abstract

    Residential heating and cooling currently account for approximately 7% of electricity consumption of India. A warming climate will increase residential cooling requirements, while heating needs will decrease which is an alarming consequence for India, which has predominantly cooling requirements. Thus, to reduce the energy and carbon footprint of Indian building sector, it is essential to assess the impact of climate change on future heating and cooling needs and develop energy-efficiency solutions. This research evaluated the effect of climate change on the heating and cooling energy needs of an archetypical residential room in India, covering all climate zones. We developed a novel approac…

  3. Related Broader context
    A Framework towards Quantifying Human Restorativeness in Virtual Built Environments
    Zhengbo Zou, Semiha Ergan · 2019 · Computers and Society · preprint, not peer reviewed · cited 11 times · Not summarized yet

    A Framework towards Quantifying Human Restorativeness studies how virtual built environments relate to restoration, rather than pollutant exposure and cognitive performance in lecture halls.

    Abstract

    The impact of built environment on the human restorativeness has long been argued; however, the interrelations between neuroscience and the built environment, and the degree to which the built environment contributes to increased human restorativeness has not been completely understood yet. Understanding the interrelations between neuroscience and the built environment is critical as 90% of time in a typical day is spent indoors and architectural features impact the productivity, health and comfort of occupants. The goal of this study is to bring a structured understanding of architecture and neuroscience interactions in designed facilities and quantification of the impact of design on human…

  4. Related Broader context
    Inverse Modeling of Climate Responses of Monumental Buildings
    R. P. Kramer, A. W. M. van Schijndel · 2012 · Computational Engineering, Finance, and Science · preprint, not peer reviewed · cited 2 times · AI summary available

    Inverse Modeling of Climate Responses models temperature and humidity in unheated monumental buildings, whereas this study measures lecture-hall air quality and cognition.

    Abstract

    The indoor climate conditions of monumental buildings are very important for the conservation of these objects. Simplified models with physical meaning are desired that are capable of simulating temperature and relative humidity. In this paper we research state-space models as methodology for the inverse modeling of climate responses of unheated monumental buildings. It is concluded that this approach is very promising for obtaining physical models and parameters of indoor climate responses. Furthermore state space models can be simulated very efficiently: the simulation duration time of a 100 year hourly based period take less than a second on an ordinary computer.

  5. Related Broader context
    Are You Comfortable Now: Deep Learning the Temporal Variation in Thermal Comfort in Winters
    Betty Lala, Srikant Manas Kala, Anmol Rastogi et al. · 2022 · Machine Learning · cited 6 times · AI summary available

    Are You Comfortable Now uses deep learning to predict temporal changes in winter thermal comfort, rather than studying ventilation, pollutants, and working memory.

    Abstract

    Indoor thermal comfort in smart buildings has a significant impact on the health and performance of occupants. Consequently, machine learning (ML) is increasingly used to solve challenges related to indoor thermal comfort. Temporal variability of thermal comfort perception is an important problem that regulates occupant well-being and energy consumption. However, in most ML-based thermal comfort studies, temporal aspects such as the time of day, circadian rhythm, and outdoor temperature are not considered. This work addresses these problems. It investigates the impact of circadian rhythm and outdoor temperature on the prediction accuracy and classification performance of ML models. The data …

  6. Related Broader context
    Studying Buildings Outlines to Assess and Predict Energy Performance in Buildings: A Probabilistic Approach
    Zohreh Shaghaghian, Fatemeh Shahsavari, Elham Delzendeh · 2021 · Applications · cited 2 times · AI summary available

    Studying Buildings Outlines predicts energy consumption from building geometry, rather than assessing ventilation conditions and student cognition.

    Abstract

    Building performance is commonly calculated during the last phases of design, where most design specifications get fixed and are unlikely to be majorly modified based on design programs. Predictive models could play a significant role in informing architects and designers of the impact of their design decisions on energy consumption in buildings during early design stages. A building outline is a significant predictor of the final energy consumption and is conceptually determined by architects in the early design phases. This paper evaluates the impact of a building's outline on energy consumption using synthetic data to achieve appropriate predictive models in estimating a building's energy…

  7. Related Broader context
    Simulation and Optimisation of Air Conditioning Systems using Machine Learning
    Rakshitha Godahewa, Chang Deng, Arnaud Prouzeau et al. · 2020 · IEEE Access 2022 · cited 15 times · AI summary available

    Simulation and Optimisation of Air Conditioning Systems uses recurrent neural networks to optimize temperature setpoints in unoccupied rooms, unlike this study’s occupied lecture halls.

    Abstract

    In building management, usually static thermal setpoints are used to maintain the inside temperature of a building at a comfortable level irrespective of its occupancy. This strategy can cause a massive amount of energy wastage and therewith increase energy related expenses. This paper explores how to optimise the setpoints used in a particular room during its unoccupied periods using machine learning approaches. We introduce a deep-learning model based on Recurrent Neural Networks (RNN) that can predict the temperatures of a future period directly where a particular room is unoccupied and by using these predicted temperatures, we define the optimal thermal setpoints to be used inside the ro…

  8. Related Shared data, tool or method
    State-Based Modeling of Buildings and Facilities
    M. Norbert Fisch, Markus Look, Claas Pinkernell et al. · 2014 · Software Engineering · preprint, not peer reviewed · cited 17 times · Not summarized yet

    State-Based Modeling of Buildings and Facilities develops a formalized method for interpreting building measurements and expected behavior, applicable to monitoring building conditions.

    Abstract

    Research on energy efficiency of today's buildings focuses on the monitoring of a building's behavior while in operation. But without a formalized description of the data measured, including their correlations and in particular the expected measurements, the full potential of the collected data can not necessarily be exploited. Who knows if a measured value is good or bad? This problem becomes more virulent as smart control systems sometimes exhibit intelligent, but unexpected behavior (e.g. starting heating at unconventional times). Therefore we defined a methodology starting already at the design of the building leading to a formalized specification of the implementation of a building's ma…

How are these papers found?

We compare the title and abstract of this paper with those of every paper summarized on this site, and with the papers Semantic Scholar recommends, those it cites and those citing it (for a much-cited paper, its most recent citations and, from OpenAlex, the most cited ones). Among the prior work and the follow-ups, the papers that use each other in depth, a method it uses and the much-cited follow-ups come a little higher. The levels (very close, close, related) come from the similarity of the texts, not from a judgment of quality; * marks a paper without an abstract, compared by its title. The sentence under a paper is written by an AI from the two abstracts: check it in the papers. A paper marked not relevant by three readers leaves the list.

Updated on 27 November 2026.

The illustrated guide to the papers around a paper

Disclaimer: The AI-based summarization tool and virtual assistant provided on this website may not always provide accurate and complete summaries or responses. We encourage you to carefully review and evaluate the generated content to ensure its quality and relevance to your needs.